Power Supply 12V/2A (DIN)
| SKU | PP-PWR-2A-DIN |
|---|---|
| Product line | PIERRE Pro |
| Category | Power Supplies |
| Manufacturer | YingJiao |
| Manufacturer SKU | YSD30S-1202000 |
| GTIN / EAN | 8606034720178 |
| HS code | 8504406020 |
Overview
The PIERRE Power Supply 12V/2A (DIN) converts mains AC to a regulated 12 V DC output rated 2.0 A, giving 24 W. It is the supply for a PIERRE controller together with the field devices on the same rail.
Input is 100-240 V AC. Protection covers overload, over-voltage and short circuit.
It clips onto 35 mm DIN rail, is rated IP20, and operates from -20 °C to +70 °C.
When sizing, add the controller's own consumption to every device it powers and leave headroom.
Key features
- 12 V DC output, 2.0 A, 24 W
- Input 100-240 V AC
- Overload, over-voltage and short-circuit protection
- 35 mm DIN rail mounting
Technical specifications
| Environmental | |
|---|---|
| Operating Temperature (°C) | -20 ~ +70 |
| Operating Humidity | 20 - 90, Non Condensing % RH |
| Operating Temperature | -4°F ~ +158°F |
| IP Rating | IP20 |
| Electrical | |
| Output Voltage | 12.0V DC, 2.0A, 24W |
| Current | 2.0 A |
| Input Power | 100-240V AC |
| Efficiency | 87 % |
| Power Factor | 0.99 |
| Connectivity | |
| Connectivity | Zigbee |
| Physical | |
| Product Color | White |
| Mounting Type | DIN |
| Wiring Requirements | N - Neutral, L - Line |
| Features | |
| LED Indicators | Yes |
| Safety | |
| Safety Features | Overload, Over Voltage, Short Circuit |
Electrical & I/O
| DIN rail | 2 module(s) |
|---|
Pin layout
| Pin | Label | Type | Position |
|---|---|---|---|
| 1 | L | power_line | top |
| 2 | N | power_neutral | top |
| 3 | 12V+ | output_12v_plus | bottom |
| 4 | GND | power_gnd_out | bottom |
Physical & packaging
| Dimensions (L × W × H) | 35 × 59 × 89 mm |
|---|---|
| Weight | 120 g |
| Box dimensions (L × W × H) | 45 × 70 × 100 mm |
| Box weight | 138 g |
User manual
- 1. Dimensions
- 2. What you need
- 3. Wiring
- 4. Functional Diagram
- 5. Derating Curve
- 6. Output Derating vs Input Voltage
1. Dimensions
- H: 89 mm
- D: 59 mm
- W: 35 mm
2. What you need
Wired. Mains AC input, DIN-rail mounted. Provides 12 V DC for PIERRE devices such as the Controller; size the supply to the total current of everything connected.
3. Wiring
- Connect the AC input terminals to mains power: L (Live) and N (Neutral).
- The power supply converts mains AC to 12 V DC; the output terminals are marked V+ and V−.
- Connect V+ to the 12 V input of the device and V− to its GND.
- Use the correct conductor cross-section and double-check polarity to avoid damaging connected devices.
| Run | Wires | Cross-section | Cable type | Conductors |
|---|---|---|---|---|
| Example: From power supply to Controller | 2 | 0.75 mm² | NYM-J | +12 V, GND |
Example wiring: From Power supply to Controller
4. Functional Diagram
Functional Diagram – System Overview
The diagram shows the internal stages of a switching mode power supply (SMPS) from AC input to regulated DC output.
Block descriptions:
- I/P (Input): AC mains voltage is supplied to the power supply.
- EMI Filter: attenuates conducted and radiated electromagnetic interference and protects downstream components.
- Rectifiers & Filter (primary side): converts AC to DC and smooths the rectified voltage with capacitive filtering.
- Power Switching Stage: a high-frequency switching converter (typically a MOSFET) chops the DC voltage to drive the transformer; switching is controlled by PWM (pulse width modulation).
- Transformer: provides galvanic isolation between input and output and steps the voltage up or down.
- Rectifiers & Filter (secondary side): converts the high-frequency AC from the transformer back to DC and filters ripple and noise. Delivers the output rails +V and –V.
- Detection Circuit: monitors the output voltage and generates the feedback for regulation.
- Control Circuit: processes the feedback and adjusts the switching duty cycle for a stable DC output.
- O.L.P. (Over Load Protection): detects overload or short circuit on the output and limits the current or shuts the converter down.
- O.V.P. (Over Voltage Protection): disables the power supply if the output voltage exceeds the set limit.
5. Derating Curve
- Load (%)
- Ambient Temperature (°C)
6. Output Derating vs Input Voltage
- Load (%)
- Input voltage (V AC), 60 Hz