Overview
The Pierre Thor – Fan Coil Touch 4" Thermostat 230V is designed for 2-pipe and 4-pipe fan coil systems with 3-speed fan control, 1 relay or 0-10V for valve control. Powered by 230V AC, it supports Modbus RTU and Zigbee integration, providing reliable and intelligent climate control for residential and commercial buildings.
Key features
Fan coil (3-speed, 1 relay or 0-10V for valve control) 2-pipe / 4-pipe FCU systems, 230V, Modbus/Zigbee, Touch screen
Technical specifications
| Certification | |
|---|---|
| CE Marking | Yes |
| RoHS Compliant | Yes |
| Warranty | 2 years |
| Control | |
| Relay Type | Dry Contact None |
| Display | |
| Touch Screen Dimension | 4 inch |
| Touch Screen Resolution | 480x480px pixels |
| Electrical | |
| Power Supply | 100-240V AC 50-60Hz |
| Power Consumption | 1.5 W |
| Environmental | |
| Operating Temperature (°C) | 0°C - +50°C |
| IP Rating | IP20 |
| Physical | |
| Width | 86 mm |
| Height | 86 mm |
| Depth | 53 mm |
| Panel Material | Tempered glass |
| Product Color | Black |
| Mounting Type | Flush mount |
| Mounting Box | 86x86x50mm |
| Connectivity | |
| Connectivity | Zigbee, Modbus |
| Safety | |
| Safety Features | Over voltage protection, Short circuit protection |
| Sensors | |
| Built-in Sensors | Temperature, Humidity |
Electrical & I/O
| Operating voltage | 230 V |
|---|---|
| Power consumption | 1.5 W |
| Max. current | 3 A |
| Connection | Modbus, Zigbee |
Wiring diagrams
Dimension drawings
Physical & packaging
| Dimensions (L × W × H) | 53 × 86 × 86 mm |
|---|
User manual
- 1. Product Description
- 2. Product Size
- 3. Technical Specification
- 4. Before Wiring and Install
- 5. Wiring
- 6. Installation
- 7. Operation
1. Product Description
- Power On/Off
- Settings
- Time
- Wave (Zigbee) Connected
- Heating
- Auto Mode
- Cooling
- Room Temperature
- Room Humidity
- Target Temperature
- Slider to adjust Temperature
2. Product Size
W - 86mm
H - 86mm
W1 - 11.5mm
W2 - 41.8mm
W - 50.3mm
H - 50.3mm
3. Technical Specification
4. Before Wiring and Install
- Read these instructions carefully. Failure to follow them may damage the product or create a hazardous condition.
- Verify that the ratings specified in these instructions and on the product are suitable for your application.
- Installation must be carried out by a trained and experienced service technician.
- After installation is complete, verify that the product operates correctly by following the procedures described in these instructions.
5. Wiring
Fan coil control
6. Installation
This thermostat is suitable for installation in a standard 86 mm back box or a European 60 mm flush-mounted box.
Accurately connect the power cable to the power terminal box
Fix the mounting plate on the cassette with a screwdriver through two screws
Hang the control panel onto the mounting plate
Installation is completed
7. Operation
Dashboard and Settings
Press the ⚙️ to enter the Settings
PIN Code
Enter the PIN code. The default code is: 692734
Settings Menu
Network – Add the thermostat to a PIERRE Wave network.
Clock – Manually set the date and time.
Mode – Configure the operating modes available to the end user.
PIN – Set or change the PIN code.
Brightness – Adjust the display brightness.
Temperature Calibration – Apply a temperature offset to calibrate the temperature sensor.
Device Information – Configure the minimum and maximum temperature limits, Modbus settings, and view device information.
Factory Reset – Restore the thermostat to its factory settings. The default PIN code will also be restored.
Pairing Mode
To add the thermostat to the PIERRE system, open the Network menu on the thermostat.
On the PIERRE Gateway, start the Add New Wave Device wizard. Then tap Search for Network on the thermostat.
Once the thermostat detects the network, follow the on-screen instructions to complete the pairing process.
Time Settings
Adjust the time settings manually.
Once the thermostat is connected to the PIERRE Gateway, the date and time will be synchronized automatically.
Operating Modes
Select the operating modes that will be available on the thermostat.
Heating – Heating only.
Cooling – Cooling only.
Heating and Cooling – Allows manual switching between Heating and Cooling modes.
Heating and Cooling with Auto Switch – Automatically switches between Heating and Cooling based on the configured temperature settings.
Select which operating modes are available to the user on the thermostat.
Change PIN Code
Change the access PIN code.
Enter the current PIN code, then enter the new PIN code twice to confirm it.
Note: The default administrator PIN code will always remain valid and can always be used to access the settings.
Brightness
Adjust the thermostat display brightness.
Temperature and Humidity Offsets
Set the temperature and humidity offsets to calibrate the thermostat's temperature and humidity readings.
Device Info
Max Set Temp – Set the maximum temperature that can be selected on the thermostat.
Min Set Temp – Set the minimum temperature that can be selected on the thermostat.
Blind Zone Temp – Set the temperature hysteresis (deadband) used for temperature regulation.
Device ID – Set the Modbus address of the thermostat.
Baud Rate – Set the baud rate for Modbus communication.
Parity – Set the parity for Modbus communication.
Zigbee Connection – Indicates whether the thermostat is connected to the PIERRE Wave Gateway.